MCOT100 Oil Dielectric Loss Test Set

Test cell adopt three-electrode-type structurZ Adopting medium frequency induction heating.

Large LCD display Measure range: 5pF-200pF (electric capacity); 1.000-30.000 (relative permittivity); 0.00001 – 100 (dielectric loss factor); 2.5 MΩm~20 TΩm (Resistivity).

Temperature setting range: 0~125℃.

AC voltage setting range: 500~2200V.

DC voltage setting range 0~500V.


Features

Major Technical Index

1) Test cell adopts three-electrode-type structure, which can eliminate the effect of stray capacitance and reduce leakage on the dielectric loss test results.

2) Adopting medium frequency induction heating and PID temperature control algorithm.

3) Internal capacitor is SF6 gas-filled three-electrode capacitance, its dielectric loss and capacitance is not affected by the ambient temperature and humidity. It can make the instrument accuracy be guaranteed after prolonged use.

4) AC test power supply using AC-DC-AC conversion, effectively avoid the fluctuations in mains voltage and frequency on dielectric loss measurement accuracy effect. Even a generator, the instrument can work properly.

5) Perfect protection function; When there is over voltage、over current or high-voltage short circuit, instruments can quickly cut off pressure, and issues a warning message. When the temperature of the sensor failure or not connected, the instrument will also issue a warning message.  There is a temperature limiting relay in the medium frequency induction heating furnace. When temperature above 120 degrees, the instrument frees the relay and stops heating. Xperimental parameter is set.

6) Temperature setting range 0~125℃, AC voltage setting range 500~2200V, DC voltage setting range 0~500V.

7) Large LCD display with backlight and clear display, Friendly human-machine interface, simply follow the Chinese characters menu prompt, enter the command, the instrument can be automatically tested, and automatically store and print test results.

8) The instrument comes with real time clock, the test date and time can be saved、displayed and printed with the test results.

9) Test cell calibration. We can judge the test cell’s cleaning and assembly by measuring electrode capacitance and dielectric loss factor of the test cell. The calibration data is automatically stored, in order to accurately calculate the relative permittivity and the DC resistivity.


  • Previous:
  • Next:

  • Power supply AC220V±10%; 50Hz/60Hz ±1%
    Measuring range
    Electric capacity 5pF~200Pf
    Relative permittivity 1.000~30.000
    Dielectric loss factor 0.00001~100
    Resistivity 2.5 MΩm~20 TΩm
    Measuring accuracy
    Electric capacity ± (1% of measuring value+0.5pF)
    Relative permittivity ±1% of measuring value
    Dielectric dissipation factor ± (1% of measuring value+0.0001)
    Resistivity ±10% of measuring value
    Resolution
    Electric capacity 0.01pF
    Relative permittivity 0.001
    Dielectric dissipation factor 0.00001
    Test temperature 0~125℃
    Error of measurement ±0.5℃
    Test Voltage AC(RMS) 500~2200V Continuously adjustable, frequency 50HZ
    Test Voltage D 0~500V Continuously adjustable
    Power 100W
    Overall dimension 500×360×420
    Total weight 22Kg